ECS / Conventional CMSI 8 zones Kara 8 Up
La Kara 8 UP ECS and CMSI is a Control and Signalling Equipment (DHW) conventional and a Fire Safety Control Centre (CMSI), designed to manage category A Fire Safety Systems (FSS) with type 1 alarm equipment (AE).
The ECS has 8 detection loops that comply with NF EN54-2 and 54-4 standards. The CMSI consists of an Alarm Management Unit (AMU) and 3 trip functions that can be configured for current emission or interruption, with or without position control.
GENERAL CHARACTERISTICS
- Detection :
- 8 32-point detection lines
- Alarm discrimination
- Dual detection
- Safety :
- 1 uGA1 evacuation zone
- 2 independent lines of sound diffusers adjustable time delay from 0 to 5 minutes
- 3 configurable enabling or disabling functions with or without position monitoring
- Connectivity :
- 1 rS-232 port
- 1 rS-485 port
- Postponement release :
- General fire alarm report
- General fault report
- 2 configurable relays
- Power supply :
- Operating voltage: 12 V
- Main source: 230 Vac
- Secondary sources :
- 1 12 V, 7 Ah maintenance-free lead battery for DHW
- 1 12 V, 1.2 Ah maintenance-free lead battery for the UGA
- 72-hour standby time, 1-hour security time, 10-minute alarm time
-
PHYSICAL CHARACTERISTICS
- - Dimensions: W 506 mm x H 300 mm x D 117 mm
- - Net weight: 6.2 kg (with batteries)
- - Material, colour: ABS, grey
- - Protection rating: IP 30
- - Operating temperature: -10 to +50°C
- Reference : 016225