4-Zone Technical Alarm
Technical alarm panels are used in all types of building (boiler rooms, lifts, technical rooms, etc.) to signal technical faults in an installation.
They signal an alarm from a normally open or normally closed potential-free contact. A dedicated indicator light shows any fault in the mains or battery power supply. The front panel can be written on to label the zones or relayed alarms.
Technical Specifications:
- Power supply: 230V 50 Hz + 10% - 15% 500 mA
- Battery life: between 12 and 30 h depending on version
- Backup power from 2 NiMH 9V 280mAh batteries
- Configuration of each input (NO or NC contacts) and time delay
- Input / repeater connection: 1 pair 8/10 (1000m max)
- Information repeater connection: 3G 1.5 mm²
- User output 19V +/-3V:60mA
- Repeater output: bus for repeaters 10540 / 10580
- Material / Colour: PC / White
- Operating temperature: -10°C to + 55°C
- Protection rating: IP 40 / IK 07
- Weight: Net - 760 g Gross - 860 g
- Dimensions: (mm) H 258 x W 166 x D 84
- Reference: 11340