Type 3 Alarm - BAAS MA Recorded Message
NF certified to reference standard NF C 48-150 of 1989
Type 3 alarm equipment consists of one or more B.A.A.S (self-contained sounder alarm units) of the Ma (on/off) type, linked together by a loop of manual call points.
The B.A.A.S Ma Me includes a sounder and a battery so that it can operate in the event of a mains power failure.
It features a pre-recorded message to inform the public by voice in French (and/or) English before broadcasting the NF S 32-001 evacuation sound signal, and it triggers the control of an interlocked device (fire door, sound system cut-off, etc.) for a minimum duration of 5 minutes.
Technical specifications:
- Power supply: 230 Vac 50 Hz + 10% - 15%
- Operating temperature: -10°C to + 55°C
- Material / Colour: PC V0 / White
- Protection rating: IP 42 / IK07
- 1 auxiliary contact: changeover 48 V / 3 A / 30 VA
- Sound output: 90 dB (Class B) NF S 32 001
- Battery pack(s): Ni-Mh 8.4V 170 mAh or 9V 280mAh
- Weight: 1250g
- Dimensions: 162x253x95mm (WxHxD)
- Reference: 11450