Type 3 Alarm + Flash - BAASL MA
NF certified to reference standard NF C 48-150 of 1989
Type 3 alarm equipment consists of one or more Ma (On/off) type B.A.A.S (self-contained sounder alarm units) linked together by a loop of manual call points.
The B.A.A.S.L Ma includes a sounder and a battery so that it can operate in the event of a "mains" power failure.
As soon as the control loop is opened, all the B.A.A.S units are triggered. It broadcasts the NF S 32-001 general alarm signal and triggers the control of an interlocked function (fire door, sound system cut-off, etc.) for a minimum of 5 minutes.
It also emits a light signal to alert deaf and hard-of-hearing people to the presence of a fire risk. This feature improves the perception of the emergency evacuation signal in noisy premises.
Technical specifications:
- Power supply: 230Vac 50 Hz + 10% - 15%
- Operating temperature: -10°C to + 55°C
- Material / Colour: PC V0 /White
- Protection rating: IP 42 / IK07
- 1 auxiliary contact: Changeover 48 V / 3 A/ 30 VA
- Sound power and tone: 90 dB (Class B) NF S 32 001
- Battery(ies): Ni-MH 8.4V 170 mAh or 9V 280mAh
- Weight: 1250g
- Dimensions: 162x253x95mm (WxHxD)
- Reference: 11470