Class 2 self-contained trigger detector with no back-up
Autonomous trigger detectors (DADs) are used to control voltage-break actuated safety devices (DASs). DADs are recommended for controlling fire doors and stairwell smoke extraction systems.
Insensitive to power cuts
Integrated installation aid (spirit level)
- Power supply: 230 Vac (+ 10% / - 15%), 50 Hz, 150 mA
- 1 loop of 2 automatic detectors
- 1 loop of 2 manual control units
- IP 42 / IK 07
- 3 slave controls (maximum power 4.5 W/Class I and 4.5 W/Class II)
- Remote control: 24 V (+/- 10%)
- 1 potential-free NO/NC alarm contact (30 V / 1A)
- Reference : 11610