Autonomous Sound Alarm Block (Main) Type 2B - 4 zones
NF-certified in accordance with reference standard NF C 48-150 of 1989
Type 2b alarm equipment consists of a Pr (Main) type box and Sa (Satellite) type B.A.A.S (Blocs Autonomes d'Alarme Sonore).
The Pr type B.A.A.S allows the creation of a category C fire safety system (S.S.I.) with type 2B alarm equipment (E.A.). It has 4 or 8 manual release loops depending on the model.
Activation of one or more manual releases triggers the panel's restricted alarm and, after a time delay or not, the general alarm process lasting a minimum of 5 minutes. Sa type B.A.A.S broadcast the NF S 32-001 general alarm signal.
Two potential-free contacts, which can be individually associated with each loop, can be used to control fire doors, public address systems, etc. They can also be set to "power off" by code during unoccupied periods.
An external control input can be used to control the start/end of class bell for schools, broadcast via Sa-type B.A.A.S. devices.
- Power supply: 230Vac 50 Hz + 10% - 15%
- Operating temperature: -10°C to + 55°C
- Material / Color: PC V0 / White
- Protection rating: IP 40 / IK 07
- 2 auxiliary contacts: Inverter 60 V / 4A
- 1 general alarm contact: 30 V / 1A changeover contact
- 1 restricted standby contact: 30 V / 1A changeover contact
- Battery(ies): Ni-Mh 8.4V 170 mAh or 9V 280 mAh
- Weight: 1680 g
- Dimensions: (mm) H 240 x W350 x D 75
- Reference : 11551