Technical Alarm 4 Zones + 2 Relays
This alarm can be used in all types of buildings, such as equipment rooms, elevators, boiler rooms, etc., to warn of technical incidents in an installation.
It signals the source of an anomaly by means of an audible signal and a specific indicator light for each alarm, and indicates any malfunction of the mains or battery power supply.
The capacity of this technical alarm is 4 alarms.
Technical specifications :
- Operating temperature: -10°C to + 55°C
- Powered by Ni/Mh battery
- 2 Programmable output relay
- Configuration of each input (NO or NC contacts) and time delay
- Configuration of each input (automatic or manual reset)
- Small footprint
- Power supply: 230 Vac 50 Hz + 10% - 15%
- Table 2 entries
- Material / Color: PC / White
- Protection rating: IP 40 / IK 07
- Input connection: 1 pair 8 or 9/10ths max 1.5mm2
- User output: 19 V +/- 3 V max 40 mA
- 2 nO or NC dry contact outputs (selectable via jumpers) max 1A 30V
- Transfer bus (max 2 transfer boards): 1pair 8 or 9 th - Batteries: Ni-Mh 9V 280 mAh
- Weight : Net - 415 g Brut - 470 g
- Dimensions: (mm) H 160 x W1120 x D 41
- Reference : 11330